Comments on: Do Programmable Thermostats Save Energy? https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/ Building science knowledge, HVAC design, & fun Sat, 20 Jul 2013 18:54:08 +0000 hourly 1 https://wordpress.org/?v=6.6.2 By: Bob https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5943 Sat, 20 Jul 2013 18:54:08 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5943 As of May 62,000 people
As of May 62,000 people signed up for Smarthours, apparently more than a few people are saving money with the programmable thermostats. 
 
http://newsok.com/oklahoma-gas-and-electric-co.s-summer-smarthours-pricing-to-begin-next-week-in-oklahoma/article/3839036

]]>
By: Bob https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5942 Sat, 20 Jul 2013 18:51:05 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5942 Tedkidd, looks like you have
Tedkidd, looks like you have an oversized HVAC unit if it only operates in 1st stage all the way to 100degrees. Most 14SEER+ systems pull about 4amps per ton @ 95F outdoor temp, so 7-8amps for your system on low speed isn’t unusual. A single stage 15SEER 2 ton would have done the job at the same cost to run and cost 1/2 the money to install. Pull the EER @ 95F of a 14+ SEER single stage and you current system. In most cases there is less than 1EER difference, however the installed price is typically twice as much.

]]>
By: Pj https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5941 Sat, 20 Jul 2013 01:29:25 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5941 Hi Allison, 
Hi Allison, 
You would not believe the amount of fraudulent savings claimed by utility programs based on their assumptions that everyone with a programmable T-Stat is setting it back 6 hrs night and day. Also, I was just (today) read a 96 item report on the problems encountered with the nest t-stat from the largest res HVAC company in the US, who by the way, is owed by an electric company. If you are interested let me know. Further, it looks like there are some new things developing on the ability to see HVAC issues from the T-Stat data signatures, check out, http://www.ecofactor.com/  
I hope you are well, 
Pj  

]]>
By: Skye Dunning https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5940 Sat, 20 Jul 2013 00:16:13 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5940 I love that!
I love that!

]]>
By: Ted Kidd https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5939 Fri, 19 Jul 2013 22:25:46 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5939 Does “Setback” save
Does “Setback” save energy?  
 
Turns out the answer to that may be as variable and fingerprints.  
 
Does “Setback” lead to larger equipment sales? Yes, yes it does. So, maybe if you look at the big picture, setback has a significant unrecognized equipment and energy cost.  
 
My buddy Cameron Taylor is finding, with his new two stage AC, that recovering from setback (comparing weekday and weekend use) may use more energy than the setback saves: 
 
“I suppose I should prime the pump a bit regarding what I see in the charts: 
 
The peak consumption days, especially notable in the 2012 data, likely coincide with electric dryer usage. After my wife saw that and a similar one in the 2013 data, we started hanging our clothes outdoors to dry. That is reflected by a lack of sharp peaks in the 2013 data from 13 June to month’s end. 
I am, in a preliminary sense, seeing little difference between the eight hour setback Monday through Friday, where the temperature setpoint goes from 75 to 78 between 0800 to 1700, and a constant setpoint of 75 maintained on weekends. Also, last year, the thermostat would set back to 76 at 2300 and back to 75 at 0600. This year it stays at 75 all night long. I would tentatively conclude, due to a combination of the building shell improvements and the two stage capabilities of the a/c system, that there isn’t much benefit or penalty from our setback scheme. 
The setback scheme did seem to indicate a modest difference in consumption last year prior to reflective roof and two stage HVAC. 
On a recent 90+ degree day in June I measured the outdoor condenser’s amp draw while it ran in 1st stage. It’s a three ton unit with the Copeland Ultratech unloading scroll. Combined amp draw between condenser fan and compressor was six amps. When I installed the Evergreen ECM blower motor on the furnace June 14, I measured its amp draw as under an amp on low speed. While I would love to have data loggers on the electric consumption of both indoor and outdoor components (would make it much easier to break out a/c consumption over base load), if the majority of the time the system pulls on average about 7 to 8 amps TOTAL to keep us comfortable even on days approaching 100 degrees, that’s pretty amazing. 
When the a/c is pulling down the house temperature in the afternoon coming out of the 78 degree setback on hot days, it runs in 2nd stage until it reaches 75, and then shifts to 1st stage. After that it alternates between 1st and 2nd until after sunset, where it then stays in 1st and finally cycles off. On weekends, when the setback never occurs, the system will run steady on 100 degree afternoons but not shift into 2nd stage. On the charts, the difference between the weekend behavior and the weekday pattern differ little. 
The highest peak in 2012 was 47 kilowatts. Highest peak in 2013 was 35. Daily average dry bulbs for both days, respectively, was 85 and 88. A warmer day on average in 2013, with electric dryer usage, yet a lower peak consumption by 17 kilowatts. 
When outdoor dry bulb averages and peaks are higher, but dew point averages and peaks are lower, consumption drops. The amount of latent load makes a difference. 
A basic observation is that we used over 30% less kilowatts in the calendar month of June this year over last year. IOW we sucked 283.66 kW less from the grid this year over last.” 
 
So, keep sizing for quick recovery. Then throw in lots of dehumidifiers to manage latent… 
 
Setback, by creating impediment to aggressive downsizing equipment, may be costing us all a LOT! 
 
 

]]>
By: Skye Dunning https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5938 Fri, 19 Jul 2013 21:42:55 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5938 There are some new &quot
There are some new “smart” thermostats that can actually save money. The Nest has a feature where it will actually turn on early to keep you out of the heat strips based on the weather forcast it gets from the internet. Also the auto-away and self-scheduling features should result in savings. It’s early days and I haven’t seen any data yet but it’s going to be interesting to see how this goes.

]]>
By: David Eakin https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5937 Fri, 19 Jul 2013 21:22:25 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5937 “When combined with a
“When combined with a power plan that varies the rate baesed on time of day programmable thermostats can be VERY efffictive tools to reduce enegy costs.” 
Bob – only if the residents’ schedule coincides with the setback times. If not, watch how fast the residents change their thermostats. 
 
Allison – one thing about programmable thermostats we see regularly around here (predominant heating climate) is that the electric bills increase when using the setback schedules. This is often because the thermostat sets the new (higher) temperature instantly from the lower setting and does not increase the temperature setting gradually. If using a heat pump, the system sees that it cannot meet the new temperature demand by heat pump alone so engages the auxiliary resistance heat strips – which drives up the electric usage. What is really needed (in heating-dominated climates) is an adaptive-recovery thermostat that automatically raises the room temperature gradually so as not to engage the auxiliary heat coils.

]]>
By: Bob Seaton https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5936 Fri, 19 Jul 2013 18:30:15 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5936 Using a programmable tstat,
Using a programmable tstat, there’s a summer strategy for controlling humidity in a vacant home (in Florida, to control mold/mildew). I call it the “Danny Parker Method”: Operate 3-5 a.m. at very low temperature setting, as described here http://www.fsec.ucf.edu/en/publications/html/fsec-cr-1487-04/ But if you try this, you’ll first need to disable the adaptive recovery mode if it’s an intelligent programmable thermostat.

]]>
By: Mark B https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5935 Fri, 19 Jul 2013 18:13:11 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5935 Your thermostat, if it is
Your thermostat, if it is like mine (it looks exactly the same), has a “learning” feature. For example in the winter if I want to take the chill off in the morning by raising the temp 5 degrees and I set it to start at 6am, it will attempt to meet that setting BY 6am requiring an actual start much earlier. When delta T between inside and outside is huge I find little to no savings by setting back at night. Very frustrating indeed. My expensive programmable is a waste as I am now the daily programmer. 
 
Personally I have a secret fascination with physics dating back to grade school thanks to Mr. Roberts, my 4th grade teacher.

]]>
By: Charles https://www.energyvanguard.com/blog/do-programmable-thermostats-save-energy/#comment-5934 Fri, 19 Jul 2013 16:05:18 +0000 http://energyvanguard.flywheelsites.com/?blog_post=do-programmable-thermostats-save-energy#comment-5934 I thought I would save money
I thought I would save money when I installed a programmable thermostat to our existing HVAC system. I diligently MATCHED ALL THE COLORED WIRES, but there were a few wires left over and I thought they must not be required. The next month we received a $600 heating bill!!! Turned out the “emergency heat” option was simply the default mode of heating. 
 
I used to build computers from scratch so I know I’m capable of following wiring instruction. It doesn’t hurt to ask for assistance in switching out a thermostat. For a few bucks extra it could save you lots of money.

]]>