Comments on: Are You Using Vent Caps for Duct Leakage Tests Yet? https://www.energyvanguard.com/blog/are-you-using-vent-caps-for-duct-leakage-tests-yet/ Building science knowledge, HVAC design, & fun Sat, 27 Jul 2013 16:49:14 +0000 hourly 1 https://wordpress.org/?v=6.6.2 By: George R https://www.energyvanguard.com/blog/are-you-using-vent-caps-for-duct-leakage-tests-yet/#comment-5432 Sat, 27 Jul 2013 16:49:14 +0000 http://energyvanguard.flywheelsites.com/?blog_post=are-you-using-vent-caps-for-duct-leakage-tests-yet#comment-5432 If the ceiling is textured do
If the ceiling is textured do you have a factor (cfm) for seal lose?

]]>
By: Allison Bailes https://www.energyvanguard.com/blog/are-you-using-vent-caps-for-duct-leakage-tests-yet/#comment-5431 Fri, 26 Jul 2013 00:11:00 +0000 http://energyvanguard.flywheelsites.com/?blog_post=are-you-using-vent-caps-for-duct-leakage-tests-yet#comment-5431 Matthew L.
Matthew L.: You can use a vent cap with weight on it. You can use duct mask on the register or grille. Or you can pull the register or grille out and seal the boot, which is now allowed for ENERGY STAR V3 new homes under revision 07.

]]>
By: Matthew Lang https://www.energyvanguard.com/blog/are-you-using-vent-caps-for-duct-leakage-tests-yet/#comment-5430 Thu, 25 Jul 2013 23:56:54 +0000 http://energyvanguard.flywheelsites.com/?blog_post=are-you-using-vent-caps-for-duct-leakage-tests-yet#comment-5430 Similar, but unrelated
Similar, but unrelated question. How do most people deal with floor registers in carpeted areas?

]]>
By: Allison Bailes https://www.energyvanguard.com/blog/are-you-using-vent-caps-for-duct-leakage-tests-yet/#comment-5429 Thu, 25 Jul 2013 23:51:34 +0000 http://energyvanguard.flywheelsites.com/?blog_post=are-you-using-vent-caps-for-duct-leakage-tests-yet#comment-5429 Steve H.:
Steve H.: Yeah, I’ve heard of that happening to someone else, too. 
 
Eric G.: That’s true. I don’t think I do it without some weight on them, though. I’ll add your advice to the article. 
 
Elizabeth G.: Indeed! I forgot to mention that as an advantage, so I’ll go back and add it to the article.

]]>
By: Eric George https://www.energyvanguard.com/blog/are-you-using-vent-caps-for-duct-leakage-tests-yet/#comment-5428 Thu, 25 Jul 2013 20:24:37 +0000 http://energyvanguard.flywheelsites.com/?blog_post=are-you-using-vent-caps-for-duct-leakage-tests-yet#comment-5428 What do you mean “Vent
What do you mean “Vent caps also don’t work on most floor vents because the register or grille will just pull out”? Why do you need to attach the vents to the registers on floors anyway? The foam weather-stripping on the vent covers provides a good seal just by the weight of the cover, but if you really need to you can put a little weight on top of it to help seal the vent to the floor. We use them every day without issues, except as you note on vaulted ceilings.

]]>